中文版 English
 
 
AM Temperature controller
HBC Environment friendly chiller
HBW Environment friendly chiller
AC Industrial chiller
AW Industrial chiller
AGS Air cooled screw type chiller
AGS Water cooled screw type chiller
AC-L Low temperature chiller
AW-L Low temperature chiller
AC-H Heat and cold chiller
AL Laser chiller
APL Series pcb chiller
AGS-L Low temperature screw chiller
AEO Series cooling machiine
AJO Series cooling machine
HL Centrifugal pump
ST Cooling tower
Now: Product > Products directory
 Products directory
AC-L series Low Temperature Chillers,a new generation refrigeration unit,specially designed by ANGES, and are widely used in medicine industry,chemical industry,bioengineering etc.The temperature is adjustable in the range of -30℃~+5℃.
 
Technical parameter:

Technical parameters of AC-L series of air cooled low temperature chillers (When T=-10℃)

Model

Item

AC-3L

AC-5L

AC-8L

AC-10L

AC-12L

AC-15L

AC-20L

AC-25L

AC-30L

AC-40L

Nominal cooling capacity

kcal/h
50HZ/60HZ

2514
3012

4023
4823

6732
8078

9440
11328

11684
14014

14160
16993

18881
22657

20119
24143

23369
28043

29405
35286

KW
50HZ/60HZ

2.92

4.68

7.83

10.98

13.59

16.47

21.96

23.40

27.18

34.20

3.50

5.61

9.39

13.17

16.30

19.76

26.35

28.08

32.61

41.04

Total input power

KW

3.18

4.86

7.25

9.4

10.9

13.47

18.8

22.55

28.5

36

Power

3PH 380V 50HZ(60HZ)

Refrigerant

Type

R22(R404A/R507)

Control method

Expansion valve

Compressor

Type

Hermetic scroll typepiston type

Power(KW)

2.25

3.75

6

7.5

9

11.25

15

18

22.5

30

Condenser

Type

Finned copper tube+low noise outer rotor fan

Evaporator

Type

Shell-and-tube-type

Chilled fluid flow

m3/h

1.41

2.26

3.78

5.31

6.57

7.96

10.61

11.31

13.13

16.53

1.69

2.71

4.54

6.36

7.88

9.55

12.73

13.57

15.76

19.83

Inlet and outlet

Pipe caliber

1"

1"

1"

1 1/2"

1-1/2"

2"

2-1/2"

2-1/2"

2-1/2"

3"

Water pump

Power(kw)

0.75

0.75

0.75

1.1

1.1

1.5

2.2

2.2

4

4

Lift(m)

20

20

20

20

20

20

20

20

25

25

Safety protection

Compressor over temperature,over current,high and low pressure,over temperature,flow switch,

phase sequence,phase-missing,exhaust Overheating,antifreezing.

Dimension

Lengthmm

930

1140

1310

1680

1680

1800

2000

2200

2200

2500

Widthmm

520

560

720

810

810

990

1130

1130

1130

1200

Heightmm

975

1040

1270

1280

1280

1680

1720

1914

2026

2250

Weight

Kg

135

175

310

450

530

750

835

920

1080

1125

Note

1. Nominal cooling capacity calculated according to:

Inlet/outlet chilled fluid temperature : -5/-10.Inlet/outlet cooling air temperature: 30/38.

2. Working condition:

The temperature range of chilled fluid is from -10 to 10.

Temperature difference between inlet and outlet chilled fluid is from 3 to 8.

It is better to run the chiller while the ambient temperature at or below 35. The above red

parameters is for the particular voltage, which need to made accordingly.

Technical parameters of AC-L series of air cooled low temperature chillers (When T=-25℃)

Model

Item

AC-3L

AC-5L

AC-8L

AC-10L

AC-12L(D)

AC-15L

AC-20L

AC-25L

AC-30L

AC-40L

Nominal cooling capacity

kcal/h
50HZ/60HZ

1005
1206

1584
1901

3310
3972

4651
5581

4988
5986

5184
6221

8628
10354

10570
12684

12435
14922

15863
19036

KW
50HZ/60HZ

1.17

1.84

3.85

5.41

5.80

6.03

10.03

12.29

14.46

18.45

1.40

2.21

4.62

6.49

6.96

7.24

12.04

14.75

17.35

22.14

Total input power

KW

3.18

4.86

7.25

9.40

10.90

13.47

18.80

22.55

28.50

36.00

Power

3PH 380V 50HZ(200V/220V/415V 50HZ/60HZ)

Refrigerant

Type

R404A(R507)

Control method

Expansion valve

Compressor

Type

Hermetic scroll typepiston type

Power(KW)

2.25

3.75

6.00

7.50

9.00

11.25

15.00

18.75

22.50

30.00

Condenser

Type

Finned copper tube+low noise outer rotor fan

Evaporator

Type

Shell-and-tube-type

Chilled fluid flow

m3/h

0.57

0.89

1.86

2.61

2.80

2.91

4.85

5.94

6.99

8.92

0.68

1.07

2.23

3.14

3.36

3.50

5.82

7.13

8.38

10.70

Inlet and outlet

Pipe caliber

1"

1"

1"

1 1/2"

1-1/2"

2"

2"

2-1/2"

2-1/2"

3"

Water pump

Power(kw)

0.75

0.75

0.75

1.10

1.10

1.50

2.20

2.20

4.00

4.00

Lift(m)

18

18

18

20

20

20

20

20

25

20

Safety protection

Compressor over temperature,over current,high and low pressure,over temperature,flow switch,

phase sequence,phase-missing,exhaust Overheating,antifreezing.

Dimension

Lengthmm

930

1140

1310

1680

1680

1800

2000

2000

2200

2500

Widthmm

520

560

720

810

810

990

1130

1130

1130

1200

Heightmm

975

1040

1270

1280

1280

1680

1720

1914

2026

2250

Weight

Kg

135

175

310

450

530

750

835

920

1080

1125

Note:

1. Nominal cooling capacity calculated according to:

Inlet/outlet chilled fluid temperature : -20℃/-25℃.Inlet/outlet cooling air temperature: 30℃/38℃.

2. Working condition:

The temperature range of chilled fluid is from -25℃ to -5℃.

Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.

It is better to run the chiller while the ambient temperature at or below 35℃. The above red

parameters is for the particular voltage, which need to made accordingly. We reserve the right to

modify the above information without further notice.

 
About Us | News | Products | Certificate | Contact Us | Support | Map Top
网站备案号:粤ICP备07068861号